Voltronic Power Giant II 3P/3P
The Voltronic Power Giant II 3P/3P UPS is engineered to deliver robust and reliable power management solutions. With a 6 pulse rectifier and a nominal voltage range of 380VAC to 415VAC, it ensures optimal performance for critical applications. Ideal for data centers, industrial facilities, and telecommunications, the Giant II 3P/3P UPS provides consistent power protection and efficiency.
Key Features
- True online double conversion with — True online double conversion with DSP control
- Output power factor 0.9, customized — Output power factor 0.9, customized up to 1.0
- Galvanic isolation eliminates common mode — Galvanic isolation eliminates common mode noise
- Conformal coating ensures operation stability
- Standard IP31 protection, optional IP42
- Sustains long-term operation for all — Sustains long-term operation for all types of loads
- Redundant design for reliability
- Temperature compensation to prolong battery — Temperature compensation to prolong battery life
- Backfeed protection guarantees safety operation
- 7” touch color LCD with — 7” touch color LCD with customized control setting
- Accepts dual-mains inputs
- Parallel capability up to 4 — Parallel capability up to 4 units
- Optional 40kA surge protection module
- Optional footmaster caster wheel available
Specifications
Electrical
| Rectifier Type | 6 pulse / 12 pulse |
| Nominal Voltage | 380VAC/400VAC/415VAC |
| Acceptable Voltage Range | 304VAC – 456VAC |
| Frequency | 50Hz ± 10% |
| TVSS | 40kA (optional) |
| Input Voltage Range | 285VAC – 475VAC |
| Battery Voltage | 384 VDC (adjustable) |
| Cold Start | Yes |
| Power Factor | 0.9, customized up to 1.0 |
| Nominal Output Voltage | 380VAC/400VAC/415VAC |
| Output Voltage Regulation | ±1% |
| Overload Capability | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Dry Contacts | 5 outputs and 4 inputs |
| Optional SNMP | Power management from SNMP manager and web browser |
| Safety | IEC62040-1:2017 |
Mechanical
| IP Protection | IP31 (default), IP42 (optional) |
| Dimensions (DxWxH) mm | 656 x 405 x 817 / 656 x 405 x 941 / 818 x 432 x 1159 / 971 x 554 x 1290 / 971 x 635 x 1326 / 1051 x 705 x 1646 |
| Net Weight (Kgs) | 120 / 145 / 193 / 278 / 365 / 471 / 573 / 650 / 735 / 790 |
| Weight | 120 / 145 / 193 / 278 / 365 / 471 / 573 / 650 / 735 / 790 |
Environmental
| Operating Temperature | 0 – 50°C |
| Storage Temperature | -25°C – 55°C |
| Humidity | 0–95% (non-condensing) |
| Altitude | 1000m |
Certifications: IEC62040-1:2017
FAQs
What are the main performance specifications of the Giant II 3P/3P UPS?
The Giant II 3P/3P UPS features a power factor of 0.9, which can be customized up to 1.0. It operates with a nominal voltage of 380VAC/400VAC/415VAC and maintains output voltage regulation within ±1%.
Is the Giant II 3P/3P UPS compatible with different battery types or solar panels?
The UPS is designed to work with a battery voltage of 384 VDC, which is adjustable. It does not directly support solar panels but can be integrated into systems that include solar power with appropriate converters.
What are the physical specifications of the Giant II 3P/3P UPS?
The dimensions of the UPS are 656 x 405 x 817 mm. It has an IP31 protection rating by default, with an optional upgrade to IP42 for enhanced protection.
What are the installation requirements for the Giant II 3P/3P UPS?
Installation requires a stable environment with an input voltage range of 285VAC to 475VAC. Ensure adequate space for ventilation and maintenance access.
What warranty is offered with the Giant II 3P/3P UPS?
Voltronic Power typically offers a standard warranty period for their UPS products, but specific terms should be confirmed with the retailer or distributor.
What certifications and standards does the Giant II 3P/3P UPS comply with?
The UPS complies with the IEC62040-1:2017 standard, ensuring it meets international safety and performance requirements.
What are the operating conditions for the Giant II 3P/3P UPS?
The UPS is designed to operate efficiently within a frequency range of 50Hz ± 10%. It should be used in environments with controlled temperature and humidity to ensure optimal performance.
What are the key features and benefits of the Giant II 3P/3P UPS?
Key features include a cold start capability and overload capability of 110% continuous running, 125% for 10 minutes, and over 150% for 1 minute. These features ensure reliability and flexibility in power management.