Felicity Solar IVEM3048-LV

Felicity Solar 3–5 kVA 110 V Single-Phase Off-Grid Solar Inverter

3 kVA
Dhs. 1,321.00
Skip to product information
Felicity Solar IVEM3048-LV

Felicity Solar 3–5 kVA 110 V Single-Phase Off-Grid Solar Inverter

Dhs. 1,321.00
Power

Felicity Solar 3–5 kVA 110 V Single-Phase Off-Grid Solar Inverter, available in 2 ratings, 3 kVA to 5 kVA. Each rating is a different machine with its own figures. Pick the one that matches your system below, then select it in the options above.

True of every rating

  • Keeps 93% of what the panels make
  • 2 Years manufacturer warranty
  • Certified to CE, ISO9001

Choose your rating

3 kVA

Model IVEM3048-LV. Full specifications are listed below.

5 kVA

Model IVEM5048-LV. Full specifications are listed below.

Full specifications shared across all 2 ratings
Motor Start Capable Yes
Max Efficiency (%) 93
Input Voltage Range (V) 90-280Vac
Max AC Input Current (A) 15
Max Operating Current (A) 15
PV Open Circuit Voltage (V) 500
Startup Voltage (V) 125
Output Frequency (Hz) 50±0.3Hz/60Hz±0.3Hz(Adjustable)
Nominal DC Voltage (V) 48
Waveform Sinusoidal (utility or generator)
AC Input Voltage (V) 110Vac
Low Line Disconnect (V) 65Vac±3V (home appliances) / 90Vac±3V (computers)
Low Line Reconnect (V) 70Vac±3V (home appliances) / 95Vac±3V (computers)
High Line Disconnect (V) 140
High Line Reconnect (V) 135
Max AC Input Voltage (V) 140
Grid Frequency (Hz) 50Hz/60Hz (auto detection)
Low Freq Disconnect (Hz) 40
Low Freq Reconnect (Hz) 42
High Freq Disconnect (Hz) 65
High Freq Reconnect (Hz) 63
Line Mode Output Waveform Same as input waveform
Short Circuit Protection Line mode: circuit breaker; battery mode: electronic circuits
Transfer Time Ms 50
Overcharge Protection Yes
PV Operating Voltage Range (V) 90V-500V
PV Startup Voltage (V) 100
Boost Charge Voltage (V) 56.4
Floating Charge Voltage (V) 54
Max Charging Voltage (V) 60
Lithium Charging Voltage (V) 60
AC Output Voltage (V) 110Vac±5%
Overload Protection 5.5s@≥150% load; 10.5s@105%~150% load
Low Battery Recovery Voltage (V) 47.0V (load < 50%) / 46.0V (load ≥ 50%)
Shutdown Voltage (V) 43.0V (load < 50%) / 42.0V (load ≥ 50%)
Operating Temperature (°C) -10°C to +50°C
Storage Temperature Range (°C) -15°C to +60°C

You may also like